Temporary Service | 5/6/2010 | 5/7/2010 | 5/7/2010 | A | PASS |
Bob Reichert
|
|
|
warren Phone #: ###-#### corrections made, t/s o/h n ok
|
Temporary Service | 5/5/2010 | 5/6/2010 | 5/6/2010 | A | FAIL |
Bob Reichert
|
|
|
warren Phone #: ###-#### called, left message, NEC 400.5 so cord only rated at 45A, 250.92 shall wire in bond bushing, 312.5 shall provide abrasion protection, 200.7 shall identify grounded conductor, 110.14 shall ensure tight connections, BCC shall post job id sticker, Note; corrections shall be made within 5 working days or further action will be taken
|
Application received | | | 5/5/2010 | | |
|
|
|
|
Issue permit | | | 5/5/2010 | | DONE |
|
|
|
|
First Notice | 5/7/2010 | 5/7/2010 | | | |
Bob Reichert
|
|
|
|