Final | 7/20/2010 | 7/21/2010 | 7/21/2010 | A | PASS |
Doug A Poedy
|
|
|
daryl - please call for access Phone #: ###-####
|
DOC - Permit Finaled | 7/21/2010 | 7/21/2010 | 7/21/2010 | P | PASS |
Doug A Poedy
|
|
|
|
Electrical Rough-In | 5/21/2010 | 5/24/2010 | 5/24/2010 | A | PASS |
Jack Frank
|
|
|
Daryl Phone #: ###-#### ok
|
Permanent Service | 5/24/2010 | 5/24/2010 | 5/24/2010 | A | PASS |
Jack Frank
|
|
|
Daryl Phone #: ###-#### p/s o/h new ok
|
Rough-In Permanent Service | 5/20/2010 | 5/21/2010 | 5/21/2010 | A | FAIL |
Jack Frank
|
|
|
Daryl Kubik ###-#### corr. 300.4(A)(1) & (D) nail plates for holes , and 11/4" for cables parallel to framing members 210.52(B) remove vacuum outlet from small appliance branch circuit, 334.23 protect all cables within 6ft of both attic accesses, 314.17 & 800.24 needs connectors for all cables at low voltage cabinet upstairs closet
|
Application received | | | 5/20/2010 | | |
|
|
|
|
Issue permit | | | 5/20/2010 | | DONE |
|
|
|
|