Final | 11/1/2010 | 11/2/2010 | 11/2/2010 | A | PASS |
Daryl DeGrange
|
|
|
Colt Phone #: ###-#### ok final
|
Rough-In Permanent Service | 6/21/2010 | 6/21/2010 | 6/21/2010 | P | PASS |
Bob Reichert
|
|
|
Colt Phone #: ###-#### corrections made ric ok, p/s to house from exsisting service, u/g n ok
|
Electrical Rough-In | 6/18/2010 | 6/18/2010 | 6/18/2010 | P | FAIL |
Bob Reichert
|
|
|
Colt Phone #: ###-#### called, bad number, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 210.52 shall install receptacle within 6' of doors (rear), 312.5 all conductors entering enclosure shall have abrasion protection, 334.23 shall protect cables within 6' of attic access, 250.86 shall ground metal boxes, 334.30 shall secure nm cable within 12" of termination at panel,110.3(B) listed equipment shall be installed per instructions (clamps at panel),BCC shall wire all boxes and provide make-up, NOTE: corrections shall be made within 5 working days or further action will be taken
|
Electrical Rough-In | 6/11/2010 | 6/11/2010 | 6/11/2010 | P | PASS |
Bob Reichert
|
|
|
Underground trench inspection please-colt Phone #: ###-#### ok to cover u/g house to garage
|
Conference | 5/24/2010 | 5/24/2010 | 5/24/2010 | P | DONE |
Bob Reichert
|
|
|
Colt Phone #: ###-#### talked about wiring and upgrading service
|
Application received | | | 5/24/2010 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 5/24/2010 | | DONE |
|
|
|
|