Final | 7/14/2010 | 7/15/2010 | 7/15/2010 | A | PASS |
Bob Reichert
|
|
|
The garage code is 5296 if the house is locked Phone #: ###-#### >> Inspection requested via web by Zane Robertson called, ok to final
|
Rough-In Permanent Service | 6/8/2010 | 6/9/2010 | 6/9/2010 | A | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: Zane Robertson Phone #: ###-#### corrections made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 6/8/2010 | 6/8/2010 | 6/8/2010 | P | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: Zane Robertson Phone #: ###-#### corrections not made, fee due
|
Reinspection Fee (no hold) | 6/8/2010 | 6/8/2010 | 6/8/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: Zane Robertson Phone #: ###-#### see fail, corrections not made
|
Rough-In Permanent Service | 6/4/2010 | 6/8/2010 | 6/8/2010 | A | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: Zane Robertson Phone #: ###-#### called, left correction notice, NEC 334.30 shall secure nm cale at intervals not exceeding 4 1/2', 334.23 shall install cables at attic access per 320.23, NOTE; corrections shall be made within 5 working days or further action will be taken
|
Application received | | | 6/4/2010 | | DONE |
|
|
|
This permit was created on the web by Zane Robertson
|