ELE-Aging Inspection | 11/29/2010 | 11/29/2010 | 11/30/2010 | | DONE |
Bob Reichert
|
|
|
see final
|
Final | 11/30/2010 | 11/30/2010 | 11/30/2010 | A | PASS |
Bob Reichert
|
|
|
ok
|
Permanent Service | 6/10/2010 | 6/10/2010 | 6/10/2010 | P | PASS |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### called contractor, corrections made, left red tag to remove illegal temp receptacle out back, p/s o/h rec ok
|
Permanent Service | 6/9/2010 | 6/10/2010 | 6/10/2010 | A | FAIL |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### called, left correction notice, NEC 250.52(A)(1) shall utilize u/g water water pipe for grounding electrode, 110.12(A) shall close unused openings, 334.30 shall secure nm cables within 12" of box, left correction notice to owner about electrical work
|
Permanent Service | 6/8/2010 | 6/9/2010 | 6/9/2010 | P | CANC |
Bob Reichert
|
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### Inspection cancelled from web by: TOM BICANDI
|
Application received | | | 6/8/2010 | | DONE |
|
|
|
This permit was created on the web by TOM BICANDI
|