Temporary Service | 6/14/2010 | 6/15/2010 | 6/15/2010 | A | PASS |
Doug A Poedy
|
|
|
ed Phone #: ###-####. T/S U/G Connect ok.
|
Temporary Service | 6/14/2010 | 6/14/2010 | 6/14/2010 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### called, left correction notice, NEC 312.5 all conductors entering enclosures shall have abrasion protection, 406.8(B) all 15 and 20A outdoor receptacles shall listed weather resistant, BCC shall affix job id sticker, Note: corrections shall be made within 5 working days, fee due
|
Reinspection Fee (no hold) | 6/14/2010 | 6/14/2010 | 6/14/2010 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### see fail
|
Application received | | | 6/14/2010 | | |
|
|
|
|
Issue permit | | | 6/14/2010 | | DONE |
|
|
|
|