Final | 8/19/2010 | 8/20/2010 | 8/20/2010 | A | PASS |
Doug A Poedy
|
|
|
ACCESS THRU THE GARAGE CODE IS 2010. Phone #: ###-#### >> Inspection requested via web by David Oliver
|
DOC - Permit Finaled | 8/20/2010 | 8/20/2010 | 8/20/2010 | P | PASS |
Doug A Poedy
|
|
|
|
Permanent Service | 7/20/2010 | 7/20/2010 | 7/20/2010 | P | PASS |
Doug A Poedy
|
|
|
P/S U/G Connect ok.
|
Final | 6/17/2010 | 6/18/2010 | 6/18/2010 | A | CANC |
Doug A Poedy
|
|
|
Inspection requested from web by: David Oliver
|
Electrical Rough-In | 6/18/2010 | 6/18/2010 | 6/18/2010 | A | PASS |
Doug A Poedy
|
|
|
Inspection requested from web by: David Oliver
|
Electrical Rough-In | 6/16/2010 | 6/16/2010 | 6/16/2010 | P | FAIL |
Bob Reichert
|
|
|
Dustin Croft is our contact for the site. Inspection requested from web by: David Oliver Phone #: ###-#### called, left correction notice, NEC 334.23, shall protect cable within 6' of attic access, 210.52 shall provide receptacle in 2' wall by stairs, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 314.20 in combustible material, boxes shall be flush with finished surface, 210.52(E)(1) shall install receptacle at back of dwelling, BCC shall provide minimum 15"x20" access hole to jetted tub per instructions, NOTE corrections shall be made within 5 working days or further action will be taken
|
Application received | | | 6/16/2010 | | DONE |
|
|
|
This permit was created on the web by David Oliver
|