Permit Information
Permit NumberELE10-01354
StatusFinaled
Name DOHERTY ELECTRIC
Site Address 950 W STATE ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: Remodel of existing building. PRovide new lights and outlets.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice2/7/20112/7/20113/15/2011 DONE
DetailsDaryl DeGrange
This permit finaled on the web by Shawna Gates
Final2/7/20112/8/20112/7/2011APASS
DetailsDaryl DeGrange
Am inspection. Contact is mike his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates final ok
Final1/31/20112/1/20112/1/2011AFAIL
DetailsDaryl DeGrange
Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates NEC. 210.8 (B) (2) All kitchen 15 and 20 ampere receptacles shall hae ground fault circuit-interrupter protection for personnel. NEC. 314.22 Surface Extension (Box extension) NEC. 314.25 Each box shall have a cover, faceplate NEC.408.4 Circuit Directory or circuit indentification. NEC. 408.7 Panel cover-unused openings for circuit breakers and switches shall be closed using identified closures.
Final1/28/20112/1/20111/31/2011ACANC
DetailsDaryl DeGrange
Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
Final1/27/20111/31/20111/28/2011ACANC
DetailsDaryl DeGrange
contact is Nick his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
Final1/27/20111/28/20111/27/2011ACANC
DetailsDaryl DeGrange
Contact is Nick, his cell no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
Electrical Rough-In1/19/20111/19/20111/19/2011PPASS
DetailsDaryl DeGrange
We need a final on the Kitchen and a ceiling inspection. The contact is Nick his no. is ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Shawna Gates ri ok ceiling in entry-assembly hall. need grounding conductor for water heater booster & secure junction box
Electrical Rough-In1/18/20111/20/20111/19/2011ACANC
DetailsDaryl DeGrange
We would like a ceiling inspection. Also Kitchen fianled. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
Electrical Rough-In1/7/20111/10/20111/10/2011APASS
DetailsDaryl DeGrange
Ceiling Inspection. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates kitchen ceiling only ri ok
Electrical Rough-In12/17/201012/20/201012/20/2010APART
DetailsBob Reichert
Ceiling inspection, 1st floor. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates soffits and walls ok
Final10/20/201010/21/201010/21/2010APART
DetailsDoug A Poedy
This is a Final for basement only so they can occupy. Please don''t final entire permit out. Please call Mike at ###-#### if you have questions. Phone #: ###-#### >> Inspection requested via web by Shawna Gates
Electrical Rough-In10/19/201010/19/201010/19/2010PPASS
DetailsBob Reichert
Nick is the onsite contact and his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates 5th floor walls and ceilings ok cover
Electrical Rough-In10/15/201010/18/201010/18/2010APASS
DetailsBob Reichert
Ceiling Inspection. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates basement ceiling only ok, corrections made
Electrical Rough-In10/12/201010/13/201010/13/2010AFAIL
DetailsBob Reichert
Ceiling inspection. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates met contractor, left correction notice, BCC no violations shall be retained, NEC 358.30(A) emt shall be supported within 3' of box, 348.30 fmc shall be supported within 12" of box and every 4 1/2'
Permanent Service9/16/20109/17/20109/17/2010PPASS
DetailsBob Reichert
Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates p/s u/g rec ok
Electrical Rough-In9/3/20109/3/20109/3/2010PPASS
DetailsBob Reichert
Bathroom wall rough in. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates correction made, prints put panel in separate room, ri ok coset walls
Electrical Rough-In9/1/20109/2/20109/2/2010AFAIL
DetailsBob Reichert
Wall rough in bathroom. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates called, left correction notice, NEC240.32 enclosures for overcurrent devices in damp locations shall comply with 312.2, BCC 4-05-31(A) panels shall not be installed in shower rooms,4-05-32 no violations shall be retained, NOTE: corrections sjhall be made within 10 working days
Electrical Rough-In8/31/20109/1/20109/1/2010APASS
DetailsBob Reichert
Chris is the onsite contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates stairwell ceilings and 2nd floor walls only ok to cover- fire alarm not approved yet, panel in bathroom, NEC 240.32 refers to 312.5
Conference8/11/20108/11/20108/12/2010ADONE
DetailsDoug A Poedy
Doug, this is for 8:00 am meeting we talked about regarding service, mike ###-####
Conference8/11/20108/11/20108/12/2010ADONE
DetailsBob Reichert
mike, ###-#### reviewed service and requirements, 414 will check with people who stickered gear
Conference7/23/20107/27/20107/27/2010ADONE
DetailsBob Reichert
This conference has been scheduled for 8:00am. Nick is the contact his no. is ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Shawna Gates talked about field evaluation for service and adding new disconnect
Electrical Rough-In7/27/20107/27/20107/27/2010APASS
DetailsBob Reichert
This conference has been scheduled for 8:00am. Nick is the contact his no. is ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Shawna Gates basement closet walls only ok to cover
Conference7/15/20107/16/20107/16/2010ADONE
DetailsBob Reichert
8:00 am conf. call scheduled with Bob. Phone #: ###-#### >> Inspection requested via web by Shawna Gates reviewed service and options to bring up to code for project
Electrical Rough-In7/13/20107/14/20107/14/2010APASS
DetailsBob Reichert
Nick is the contract his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates basement walls only ok, service can't be changed because of too many disconnects without main, also ampacity of bus would be exceeded, several other violations regarding foreign piping over electrical gear, and remote service panel not correctly wired, shall meet requirements of NEC article 230, part V.
Application received  6/18/2010 DONE
This permit was created on the web by Shawna Gates