Final | 4/8/2011 | 4/8/2011 | 4/8/2011 | P | PASS |
Daryl DeGrange
|
|
|
We are ready for a Final inspection on this. All repairs have been taken care of. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate
|
ELE-Aging Inspection | 4/8/2011 | 4/8/2011 | 4/8/2011 | | DONE |
Daryl DeGrange
|
|
|
electical contractor is ready for final
|
Rough-In Permanent Service | 7/30/2010 | 8/3/2010 | 8/3/2010 | P | PASS |
Bob Reichert
|
|
|
Todd is the Wireman at ###-####. The Home Owner will be on-site in the afternoon to allow for access. Thank you. Please Final when complete. Phone #: ###-#### >> Inspection requested via web by Clint Tate corrections made, ri ok, p/s u/g rec ok
|
Rough-In Permanent Service | 7/27/2010 | 7/28/2010 | 7/28/2010 | P | FAIL |
Bob Reichert
|
|
|
Ready for Service Inspection and please Final when complete. Our wireman is Todd at ###-####. He will not be on site but reachable via telephone. The Home Owner will be home for access to the Panel in the Basement. Phone #: ###-#### >> Inspection requested via web by Clint Tate called, left correction notice, NEC 230.66 service equipment shall be marked as being suitable for service equipment, 250.24(A) grounding electrode conductor shall be connected to grounded conductor, 110.12(A) unused openings shall be closed, 408.4 shall provided circuit directory that is clear, concise, and fully explanatory, 312.5 conductors entering enclosures shall have abrasion protection, 210.52(A)(1) shall connect incoming water pipe to service within 5' of entering building, NOTE corrections shall be made within 5 working days or further action will be taken such as removal of power
|
Application received | | | 7/16/2010 | | DONE |
|
|
|
This permit was created on the web by Clint Tate
|