Final | 9/23/2010 | 9/24/2010 | 9/24/2010 | A | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI
|
DOC - Permit Finaled | 9/24/2010 | 9/24/2010 | 9/24/2010 | P | PASS |
Doug A Poedy
|
|
|
|
Final | 9/22/2010 | 9/22/2010 | 9/22/2010 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI called, left correction notice, NEC 110.12(A) shall close unused openings in panel, 210.52(B)(2) there shall be no other outlets on small appliance branch circuit, 210.52(C)(4) countertop separated by sink shall be considered separate, 210.52(A)(1) shall provide convenience outlet in bar (island)
|
Rough-In Permanent Service | 7/22/2010 | 7/23/2010 | 7/23/2010 | A | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI. P/S U/G Connect ok. Ok to cover.
|
Rough-In Permanent Service | 7/21/2010 | 7/22/2010 | 7/22/2010 | P | CANC |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI
|
Application received | | | 7/21/2010 | | DONE |
|
|
|
This permit was created on the web by TOM BICANDI
|