Electrical Permit - New: New Construction
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/12/20109/13/20109/13/2010APASS
DetailsJack Frank
Phone #: ###-#### >> Inspection requested via web by Josh Craig
Final9/9/20109/9/20109/9/2010PFAIL
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Josh Craig n talked with contractor, left correction notice, NEC 408.4 circuit directory shall agree with panel marks, 110.26 shall provide work space in front of panel, 210.52(A)(2) shall provide convenience outlet under bar, NOTE corrections shall be made within 5 working days
Rough-In Permanent Service8/4/20108/5/20108/5/2010APASS
DetailsBob Reichert
Phone #: ###-#### >> Inspection requested via web by Josh Craig ri ok, p/s u/g n ok
Application received  8/2/2010 DONE
This permit was created on the web by Josh Craig