Final | 10/4/2010 | 10/4/2010 | 10/4/2010 | P | PASS |
Bob Reichert
|
|
|
Bob Phone #: ###-#### corerections made, ok final, signed card
|
Change Status to I | | | 10/4/2010 | | DONE |
|
|
|
was finaled by mistake 9-28-10
|
DOC - Permit Finaled | 9/28/2010 | 9/28/2010 | 9/28/2010 | P | CANC |
Doug A Poedy
|
|
|
|
Final | 9/28/2010 | 9/28/2010 | 9/28/2010 | P | FAIL |
Doug A Poedy
|
|
|
larry Phone #: ###-####. Reverse polarity in 4 receptacles.
|
Electrical Rough-In | 9/16/2010 | 9/17/2010 | 9/17/2010 | A | PASS |
Jack Frank
|
|
|
Ted Phone #: ###-####
|
Electrical Rough-In | 9/15/2010 | 9/15/2010 | 9/15/2010 | P | FAIL |
Doug A Poedy
|
|
|
Larry Phone #: ###-####. Needs strapping within 12 inches of box. Needs broken mc cable fixed. Needs fine thread ground screws. Work done by non-electrician. Owner said he would bring in his electrician. Next time is $1000 dollar fine for worker and $1000 fine for owner.
|
Application received | | | 9/15/2010 | | |
|
|
|
|
Issue & PRINT permit | | | 9/15/2010 | | DONE |
|
|
|
|
First Notice | 10/4/2010 | 10/4/2010 | | | |
Bob Reichert
|
|
|
|
First Notice | 9/28/2010 | 9/28/2010 | | | |
Doug A Poedy
|
|
|
|