Final | 11/2/2010 | 11/3/2010 | 11/3/2010 | A | PASS |
Bob Reichert
|
|
|
Code 1290, if you have any questions, please call Clay. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan ok final
|
Rough-In Permanent Service | 9/21/2010 | 9/22/2010 | 9/22/2010 | A | PASS |
Jack Frank
|
|
|
Should be open, lock box on the back if not code 1290. Any questions, please call Clay. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan r/i 1st floor wiring ok p/s u/g rec. ok
|
Rough-In Permanent Service | 9/20/2010 | 9/21/2010 | 9/21/2010 | A | FAIL |
Doug A Poedy
|
|
|
Should be open, if not, lock box code 1290, any questions, please call Clay. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan. Left correction notice on-site. NEC 800.133 a2, NEC 300.4 need more nailplates, NEC 200.7 Re-identify nuetral, NEC 250.94 Intersystem bonding bar, Boise city code requires 2 ground rods even with water pipe ground.
|
Application received | | | 9/16/2010 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|