ELE-Aging Inspection | 5/4/2011 | 5/4/2011 | 5/4/2011 | | CANC |
Daryl DeGrange
|
|
|
|
Final | 5/4/2011 | 5/4/2011 | 5/4/2011 | P | PASS |
Daryl DeGrange
|
|
|
final ok
|
Rough-In Permanent Service | 9/19/2010 | 9/20/2010 | 9/20/2010 | A | PASS |
Bob Reichert
|
|
|
call for access Phone #: ###-#### >> Inspection requested via web by John VanZandt corrections made ri ok, p/s o/h rec ok
|
Rough-In Permanent Service | 9/16/2010 | 9/17/2010 | 9/17/2010 | A | FAIL |
Bob Reichert
|
|
|
call for access Phone #: ###-#### >> Inspection requested via web by John VanZandt called left correction notice, NEC 408.4 shall provide circuit directory, 110.12(A) shall close openings in panel, 250.52(A)(1) shall use interior metal water piping for grounding electrode, 250.56 rod electrodes shall be 6' apart, 210.52 shall provide receptace for closet wall over 2', 110.14(A) shall connect all strands copper to lug at service, 334.15 shall protect cable at water heater and provide disconnect, NOTE corrections shall be made in 5 working days
|