Final | 10/13/2010 | 10/13/2010 | 10/13/2010 | P | PASS |
Bob Reichert
|
|
|
Call for access Phone #: ###-#### >> Inspection requested via web by daniel bibikov corrections made, ok final
|
Rough-In Permanent Service | 10/6/2010 | 10/7/2010 | 10/7/2010 | A | FAIL |
Bob Reichert
|
|
|
Daniel-please call for access--this is solar system Phone #: ###-#### called, left correction notice, NEC 690.14(C)(2) disconnect shall be marked to identify solar voltaic system disconnect, 690.14(C)(5) shall group disconnects, 690.56(B) shall provide plaque to identify service disconnecting means, 690.4(D) shall provide listing and identification Note: corrections shall be made in 5 working days or further action will be taken
|
Application received | | | 10/6/2010 | | |
|
|
|
|
Issue & PRINT permit | | | 10/6/2010 | | DONE |
Barbara Stitt
|
|
|
|