Case Summary (ELE) | | | 6/1/2016 | | DONE |
|
|
|
|
First Notice | 10/11/2010 | 10/11/2010 | 2/14/2011 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Deb Gooden
|
Temporary Service | 10/11/2010 | 10/11/2010 | 10/11/2010 | P | PASS |
Bob Reichert
|
|
|
Contact: Garrett Collins Phone #: ###-#### >> Inspection requested via web by Deb Gooden corrections made, t/s o/h n ok
|
Temporary Service | 10/8/2010 | 10/11/2010 | 10/11/2010 | A | FAIL |
Bob Reichert
|
|
|
Contact Garrett Collins Phone #: ###-#### >> Inspection requested via web by Shelli Daylong called, left correction notice, NEC 406.8(B) 15 and 20A receptacles shall be listed WR type, 400.5(A) 3 conductor no. 6 per column A is 45A, 400.10 shall provide cable protection so tension is not transmitted to joints or terminals, 230.42(B) shall provide conductors per rating of service disconnect at trailer
|
Application received | | | 10/8/2010 | | DONE |
|
|
|
This permit was created on the web by Shelli Daylong
|