Final | 12/6/2010 | 12/6/2010 | 12/6/2010 | P | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot
|
DOC - Permit Finaled | 12/6/2010 | 12/6/2010 | 12/6/2010 | P | PASS |
Doug A Poedy
|
|
|
|
Rough-In Permanent Service | 11/12/2010 | 11/15/2010 | 11/15/2010 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot still needs bond bushing installed r/i ok
|
Rough-In Permanent Service | 11/11/2010 | 11/12/2010 | 11/12/2010 | A | FAIL |
Jack Frank
|
|
|
Rough and service of new shop Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot 110.26(F)(1) remove low voltage cable from panel space, u/g covered before inspection 314.3,28,43 needs bond bushing for steel fitting, remove screws from inside of box , provide box of proper size for conduit entries talked with contractor
|
Reinspection Fee (no hold) | 11/12/2010 | 11/12/2010 | 11/12/2010 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot u/g covered before inspection
|
Application received | | | 11/10/2010 | | DONE |
|
|
|
This permit was created on the web by Barbara Szurgot
|