Final | 2/3/2011 | 2/4/2011 | 2/4/2011 | A | PASS |
Jack Frank
|
|
|
Final inspection for basement remodle. home owner, Shanda Palsulich #208.484.3823 >> Inspection requested via web by Billy Ellison
|
Electrical Rough-In | 12/9/2010 | 12/9/2010 | 12/9/2010 | P | PASS |
Jack Frank
|
|
|
billy - late afternoon please Phone #: ###-####
|
Electrical Rough-In | 12/8/2010 | 12/8/2010 | 12/8/2010 | P | FAIL |
Bob Reichert
|
|
|
Billy or ###-#### Shanda Phone #: ###-#### called, left correction notice, BCC shall provide at least 6 rooms on permit, all make-up shall be done, NEC 300.14 shall provide 6" free conductor length at all boxes, 210.52 shall provide receptacle in 2' wall space, 334.30 shall secure cable within 12" of panel, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, Note: corrections shall be made within 5 working days
|
Application received | | | 12/8/2010 | | |
|
|
|
|
Issue & PRINT permit | | | 12/8/2010 | | DONE |
Barbara Stitt
|
|
|
|