First Notice | 3/9/2011 | 3/9/2011 | 2/1/2012 | | DONE |
Jack Frank
|
|
|
This permit finaled on the web by fred lopez
|
Electrical Rough-In | 3/8/2011 | 3/9/2011 | 3/9/2011 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by fred lopez
|
Final | 3/9/2011 | 3/9/2011 | 3/9/2011 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by fred lopez ok card signed
|
Final | 3/8/2011 | 3/8/2011 | 3/8/2011 | P | NR |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by fred lopez
|
Electrical Rough-In | 3/8/2011 | 3/8/2011 | 3/8/2011 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by fred lopez support all cables 300.11, 250.66 needs #4 copper tor GEC and water bond
|
Electrical Rough-In | 3/7/2011 | 3/7/2011 | 3/7/2011 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by fred lopez shall not use grid too support MC 300.11
|
Electrical Rough-In | 2/3/2011 | 2/3/2011 | 2/3/2011 | P | PASS |
Jack Frank
|
|
|
Enter through maintainance entrance south of dollars east of Sears Phone #: ###-#### >> Inspection requested via web by fred lopez
|
Electrical Rough-In | 2/3/2011 | 2/3/2011 | 2/3/2011 | P | PASS |
Jack Frank
|
|
|
Enter through maintainance entrance south of dollars east of Sears Phone #: ###-#### >> Inspection requested via web by fred lopez stock area walls
|
Electrical Rough-In | 1/31/2011 | 1/31/2011 | 1/31/2011 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by fred lopez walls ceiling except for store rm
|
Electrical Rough-In | 1/28/2011 | 1/28/2011 | 1/28/2011 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by fred lopez met contractor, NEC 330.30(B) shall secure mc cable within 12" of termination, using cut in emergency fixtures, check license for Fred, his was expired, told to call for am inspections
|
Owner Supplied Equipment | | | 1/19/2011 | | |
|
|
|
|
Application received | | | 1/19/2011 | | DONE |
|
|
|
This permit was created on the web by fred lopez
|