Permit Information
Permit NumberELE11-00164
StatusExpired
Name BAUMBACH LUCAS
Site Address 826 N ROSS ST
Project Name 
Customer Number 
ePlanReviewNo
Description
to turn on service
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Aging Inspection5/8/20125/8/20125/8/2012 PASS
DetailsDaryl DeGrange
permit Doc expired
DOC - Permit Expired5/8/20125/8/20125/8/2012PPASS
DetailsDaryl DeGrange
Job taken over, permited,and completed by licensed electrical contractor
ELE-Aging Inspection2/7/20122/7/20122/7/2012 FAIL
DetailsDaryl DeGrange
Corrections not completed, No activity
ELE-Aging Inspection10/5/201110/5/201110/10/2011 DONE
DetailsDaryl DeGrange
still under construction
Permanent Service2/1/20112/1/20112/1/2011PFAIL
DetailsDaryl DeGrange
Lucas Phone #: ###-#### NEC. The electrode shall be installed in such that at least (8ft) of length is in contact with the soil. NEC.250.64 (c)Grounding electrode conductor shall be installed in one continuous length without a splice or joint. Unable to inspect indoor panel
Permanent Service1/28/20111/28/20112/1/2011PNR
DetailsDaryl DeGrange
Lucas Phone #: ###-#### has not made corrections
Rough-In Permanent Service1/27/20111/28/20111/28/2011AFAIL
DetailsBob Reichert
late am please//Lucas ###-#### called, talked with owner for correction notice, referred to BCC 4-05-32 no violations shall be retained, ground rods shall be minimum 6' apart, there shall be no foreign piping below panel, shall not use metal romex connector for grounding electrode conductor, shall strap riser within 3' of service, need to see sub-panel and verify water pipe ground
Application received  1/27/2011  
Issue PAID IN FULL permit  1/27/2011 DONE