ELE-Aging Inspection | 5/8/2012 | 5/8/2012 | 5/8/2012 | | PASS |
Daryl DeGrange
|
|
|
permit Doc expired
|
DOC - Permit Expired | 5/8/2012 | 5/8/2012 | 5/8/2012 | P | PASS |
Daryl DeGrange
|
|
|
Job taken over, permited,and completed by licensed electrical contractor
|
ELE-Aging Inspection | 2/7/2012 | 2/7/2012 | 2/7/2012 | | FAIL |
Daryl DeGrange
|
|
|
Corrections not completed, No activity
|
ELE-Aging Inspection | 10/5/2011 | 10/5/2011 | 10/10/2011 | | DONE |
Daryl DeGrange
|
|
|
still under construction
|
Permanent Service | 2/1/2011 | 2/1/2011 | 2/1/2011 | P | FAIL |
Daryl DeGrange
|
|
|
Lucas Phone #: ###-#### NEC. The electrode shall be installed in such that at least (8ft) of length is in contact with the soil. NEC.250.64 (c)Grounding electrode conductor shall be installed in one continuous length without a splice or joint. Unable to inspect indoor panel
|
Permanent Service | 1/28/2011 | 1/28/2011 | 2/1/2011 | P | NR |
Daryl DeGrange
|
|
|
Lucas Phone #: ###-#### has not made corrections
|
Rough-In Permanent Service | 1/27/2011 | 1/28/2011 | 1/28/2011 | A | FAIL |
Bob Reichert
|
|
|
late am please//Lucas ###-#### called, talked with owner for correction notice, referred to BCC 4-05-32 no violations shall be retained, ground rods shall be minimum 6' apart, there shall be no foreign piping below panel, shall not use metal romex connector for grounding electrode conductor, shall strap riser within 3' of service, need to see sub-panel and verify water pipe ground
|
Application received | | | 1/27/2011 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 1/27/2011 | | DONE |
|
|
|
|