First Notice | 4/19/2011 | 4/19/2011 | 3/19/2013 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Sean DeLacy
|
ELE-Aging Inspection | 4/18/2011 | 4/18/2011 | 4/19/2011 | | DONE |
Bob Reichert
|
|
|
see final
|
Final | 4/19/2011 | 4/19/2011 | 4/19/2011 | P | PASS |
Bob Reichert
|
|
|
ok
|
Permanent Service | 2/15/2011 | 2/16/2011 | 2/16/2011 | A | PASS |
Bob Reichert
|
|
|
>> Inspection requested via web by Tyler Bowen p/s u/g n ok
|
Final | 2/3/2011 | 2/3/2011 | 2/3/2011 | P | CANC |
Bob Reichert
|
|
|
final Phone #: ###-#### >> Inspection requested via web by Tyler Bowen called and explained that the paper work for the field evaluation for the antenna package shall be received prior to inspection
|
Permanent Service | 2/1/2011 | 2/2/2011 | 2/2/2011 | P | FAIL |
Bob Reichert
|
|
|
underground and permanent service inspection on meter main pedistal. Phone #: ###-#### >> Inspection requested via web by Tyler Bowen called, 6' spacing on ground rods, replace 2 hole romex connector, verify available fault current, verify listed equipment, change breaker to 15a, verify electrical contractor hooking up equipment has permit
|
Application received | | | 1/31/2011 | | DONE |
|
|
|
This permit was created on the web by Tyler Bowen
|