First Notice | 4/21/2011 | 4/21/2011 | 5/26/2011 | | DONE |
Jack Frank
|
|
|
|
Final | 4/20/2011 | 4/21/2011 | 4/21/2011 | A | PASS |
Jack Frank
|
|
|
REINSPECTION PLEASE - CORRECTION DONE. THANK YOU Phone #: ###-#### >> Inspection requested via web by Dave Koeppen ok card signed
|
Final | 4/19/2011 | 4/20/2011 | 4/20/2011 | A | PART |
Jack Frank
|
|
|
Final inspection please Electrician Brian ###-#### Phone #: ###-#### >> Inspection requested via web by Dave Koeppen t/o ok card signed
|
Electrical Rough-In | 4/5/2011 | 4/5/2011 | 4/5/2011 | P | PASS |
Jack Frank
|
|
|
Reinspection please - errors fixed - ASAP if possible. Thank You Phone #: ###-#### >> Inspection requested via web by Dave Koeppen
|
Electrical Rough-In | 4/4/2011 | 4/4/2011 | 4/4/2011 | P | FAIL |
Bob Reichert
|
|
|
Late afternoon if possible. Electrician Brian ###-#### Phone #: ###-#### >> Inspection requested via web by Dave Koeppen met electrician, NEC 330.30 (B) shall secure cable within 12" of termination since ceiling not accessible
|
Electrical Rough-In | 3/29/2011 | 3/29/2011 | 3/29/2011 | P | PASS |
Jack Frank
|
|
|
UNDERGROUND INSPECTION PLEASE - ELECTRICIAN BRIAN ###-#### Phone #: ###-#### >> Inspection requested via web by Dave Koeppen
|
Electrical Rough-In | 3/21/2011 | 3/22/2011 | 3/22/2011 | A | PART |
Bob Reichert
|
|
|
Partial cover for Mechanical, Panel and bathroom Please, Brian Mckinney Electrician ###-#### Phone #: ###-#### >> Inspection requested via web by Dave Koeppen ok cover bath walls and ceiling and mech room walls only anop
|
Application received | | | 2/23/2011 | | DONE |
|
|
|
This permit was created on the web by Dave Koeppen
|