Temporary Service | 2/28/2011 | 2/28/2011 | 2/28/2011 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Rohl t/s u/g n ok
|
Temporary Service | 2/25/2011 | 2/28/2011 | 2/28/2011 | A | FAIL |
Bob Reichert
|
|
|
TANK U Phone #: ###-#### >> Inspection requested via web by Dan Rohl called, left correction notice, NEC 406.8(B)(1) all 15 and 20A receptacles shall be listed weather resistant type, 312.5 all conductors entering enclosures shall have abrasion protection. Note: added comment that esc card shall be posted
|
Application received | | | 2/25/2011 | | DONE |
|
|
|
This permit was created on the web by Dan Rohl
|