First Notice | 5/10/2011 | 5/10/2011 | 5/17/2011 | | DONE |
Daryl DeGrange
|
|
|
|
Final | 5/10/2011 | 5/10/2011 | 5/10/2011 | P | PASS |
Daryl DeGrange
|
|
|
Rowdy Phone #: ###-#### final ok
|
Override - Parcel Holds | 5/10/2011 | 1/1/1900 | 5/10/2011 | | |
|
|
|
Ele final only
|
Final | 4/28/2011 | 4/28/2011 | 4/28/2011 | P | NR |
Daryl DeGrange
|
|
|
the address is actually suite 50 Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe NEC 408.4 circuit directory-- 5- dead receptacles-no breaker tripped
|
Electrical Rough-In | 3/10/2011 | 3/11/2011 | 3/11/2011 | A | PASS |
Daryl DeGrange
|
|
|
will be ready at 9am for rough re-inspection. the address for this is suite 50 not 200 sorry about that Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe rough-in ok drip panning is required under sprinkler line close to panel foot print.
|
Electrical Rough-In | 3/7/2011 | 3/8/2011 | 3/8/2011 | A | FAIL |
Bob Reichert
|
|
|
contact Rowdy with any questions please. Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe called contractor, 1 1/4" issues- shall provide nailplates for holes bored,1 1/4" protection cables on studs, no piping over panel, will do ceiling later
|
Application received | | | 3/7/2011 | | DONE |
|
|
|
This permit was created on the web by Rowdy Monroe
|