First Notice | 4/27/2011 | 4/27/2011 | 5/27/2011 | | DONE |
Daryl DeGrange
|
|
|
|
Final | 4/26/2011 | 4/27/2011 | 4/27/2011 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin final ok
|
Electrical Rough-In | 4/19/2011 | 4/19/2011 | 4/19/2011 | P | PASS |
Bob Reichert
|
|
|
re-inspect ceiling Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin corrections made, ok cover ceiling
|
Electrical Rough-In | 4/18/2011 | 4/19/2011 | 4/19/2011 | A | FAIL |
Bob Reichert
|
|
|
ceiling close Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin left correction notice, told contractor, NEC 725.25 abandoned lv cable shall be removed, 300.11(B) raceways shall not be supported by other raceways, 358.30(A) emt shall be supported within 3' of box, 348.30(A) fmc shall be supported within 12" of box, 330.30(B) mc shall be supported within 12" of box
|
Electrical Rough-In | 3/25/2011 | 3/25/2011 | 3/25/2011 | P | PASS |
Daryl DeGrange
|
|
|
walls Phone #: ###-#### >> Inspection requested via web by Bryan McLaughlin rough-in ok walls and ok cover trenchs
|
Owner Supplied Equipment | | | 3/16/2011 | | |
|
|
|
|
Application received | | | 3/16/2011 | | DONE |
|
|
|
This permit was created on the web by Bryan McLaughlin
|