Final | 4/5/2011 | 4/6/2011 | 4/6/2011 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by steve cooper t/s u/g new ok
|
Final | 4/4/2011 | 4/4/2011 | 4/4/2011 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by steve cooper entered twice
|
Final | 4/4/2011 | 4/4/2011 | 4/4/2011 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by steve cooper called, left correction notice, NEC 406.8(B) receptacle shall be listed weather resistasnt type, 250.53(G) upper end of electrode shall be flush with ground, BCC shall post job id sticker, shall post address, fee due
|
Reinspection Fee (no hold) | 4/4/2011 | 4/4/2011 | 4/4/2011 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by steve cooper see fail
|
Application received | | | 4/4/2011 | | DONE |
|
|
|
This permit was created on the web by steve cooper
|