Final | 8/25/2011 | 8/25/2011 | 8/25/2011 | P | PASS |
Bob Reichert
|
|
|
call prior to arrival---Victoria Phone #: ###-#### corrections made, ok final
|
Final | 8/23/2011 | 8/24/2011 | 8/24/2011 | A | FAIL |
Bob Reichert
|
|
|
Victoria Phone #: ###-#### called, left correction notice, too many violations to list each code article, will supply on request, NEC and BCC, shall staple and protect ground conductor at service, shall provide in-use cover and weather proof box for front receptacle, all fixtures shall be mounted, closet fixture sahll be minimum 6" from shelf, shall provide 2 small appliance branch circuits and be gfci protected in kitchen, shall provide water heater disconnect, outlet up bedroom shall operate, main service shall have dead front installed and circuit schedule,dining room shall be gfci protected, shall provide 3' minimum access around outlets, only owner shall do any electrical work
|
Electrical Rough-In | 5/31/2011 | 6/1/2011 | 6/1/2011 | P | PASS |
Bob Reichert
|
|
|
victoria - please call 1/2 hr prior Phone #: ###-#### ok over main floor and upstairs
|
Electrical Rough-In | 5/16/2011 | 5/17/2011 | 5/16/2011 | A | PASS |
Bob Reichert
|
|
|
victoria Phone #: ###-#### ri kitchen only
|
Electrical Rough-In | 5/12/2011 | 5/13/2011 | 5/13/2011 | A | FAIL |
Bob Reichert
|
|
|
Victoria Phone #: ###-#### called, told to provide tails for grounds, staple wire, close openings,make-up, mount box in kitchen
|
Electrical Rough-In | 4/29/2011 | 5/2/2011 | 5/2/2011 | A | PASS |
Bob Reichert
|
|
|
victoria Phone #: ###-#### down stairs only ok cover
|
Electrical Rough-In | 4/28/2011 | 4/29/2011 | 4/29/2011 | P | PART |
Bob Reichert
|
|
|
late pm//call when on way//Victoria ###-#### ok cover walls, need to see make-up
|
Conference | 4/21/2011 | 4/21/2011 | 4/21/2011 | P | DONE |
Jack Frank
|
|
|
met with Doug and owner for conference for 2 hours 04-20-11
|
Issue PAID IN FULL permit | | | 4/14/2011 | | DONE |
|
|
|
|
Application received | | | 4/13/2011 | | |
|
|
|
|