Final | 4/27/2011 | 4/28/2011 | 4/28/2011 | A | PASS |
Bob Reichert
|
|
|
corrections are done please call me for the code to enter the house. Rick Phone #: ###-#### >> Inspection requested via web by Rick Beckman corrections made, p/s o/h rec ok
|
Permanent Service | 4/15/2011 | 4/15/2011 | 4/15/2011 | A | FAIL |
Bob Reichert
|
|
|
Please contact Rick for code to enter home. No tenants Phone #: ###-#### >> Inspection requested via web by Rick Beckman called, left message, left correction notice, NEC 230.24(B) service drop shall be 10' above accessible surface, shall bring all grounding up to code
|
Application received | | | 4/15/2011 | | DONE |
|
|
|
This permit was created on the web by Rick Beckman
|