Temporary Service | 5/10/2011 | 5/10/2011 | 5/10/2011 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk corrections made, t/s u/g n ok
|
Temporary Service | 5/3/2011 | 5/3/2011 | 5/3/2011 | P | CANC |
Bob Reichert
|
|
|
Alan Phone #: ###-#### contractor called, not ready
|
Temporary Service | 5/2/2011 | 5/3/2011 | 5/3/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk called, left correction notice, NEC 250.53(G) shall drive in ground rod until flush with or below ground
|
Application received | | | 5/2/2011 | | DONE |
|
|
|
This permit was created on the web by Alan Lusk
|