Final | 6/28/2011 | 6/29/2011 | 6/29/2011 | A | PASS |
Jack Frank
|
|
|
ok
|
Final | 6/28/2011 | 6/28/2011 | 6/28/2011 | P | CANC |
Jack Frank
|
|
|
darrel Phone #: ###-#### see added am request for 6-29-11
|
Final | 6/27/2011 | 6/28/2011 | 6/28/2011 | A | NR |
Jack Frank
|
|
|
|
Final | 6/27/2011 | 6/27/2011 | 6/27/2011 | P | NR |
Jack Frank
|
|
|
Darrel Phone #: ###-#### called
|
Final | 6/24/2011 | 6/27/2011 | 6/27/2011 | A | NR |
Jack Frank
|
|
|
darrel Phone #: ###-#### needs 50% energy for lighting
|
Permanent Service | 5/6/2011 | 5/9/2011 | 5/9/2011 | A | PASS |
Bob Reichert
|
|
|
daryl Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 5/9/2011 | 5/9/2011 | 5/9/2011 | A | PASS |
Bob Reichert
|
|
|
daryl Phone #: ###-#### corrections made, ri ok
|
Electrical Rough-In | 5/5/2011 | 5/6/2011 | 5/6/2011 | A | FAIL |
Bob Reichert
|
|
|
daryl Phone #: ###-#### called, left correction notice, NEC 334.30 shall secure nm cable within 12" of boxes, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, BCC shall terminate wiring in boxes
|
Application received | | | 5/5/2011 | | |
|
|
|
|
Issue permit | | | 5/5/2011 | | DONE |
|
|
|
|