Final | 12/30/2011 | 12/30/2011 | 12/30/2011 | P | PASS |
Doug A Poedy
|
|
|
Dave Phone #: ###-####. Internal components replaced. Service looks good. P/S connect ok.
|
Permanent Service | 6/8/2011 | 6/9/2011 | 6/9/2011 | A | PASS |
Daryl DeGrange
|
|
|
Steve Phone #: ###-#### p/s o/h rec ok
|
Permanent Service | 6/3/2011 | 6/3/2011 | 6/3/2011 | P | FAIL |
Daryl DeGrange
|
|
|
###-#### - katie NEC 230.79 (C) For a one family dwelling the service disconnecting means shall have a rating of an not less than 100 ampere,3 wire. NEC250.56 A single electrode that does not have a resitance of 25 ohms or less shall be augmented by one additional electrode 6 feet apart. Sub-panel in unit 2126 is feed by tri-plex, needsquad-plex for a subpanel. Water pipe bond if incoming water line is metal.
|
Application received | | | 6/3/2011 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/3/2011 | | DONE |
|
|
|
|