ELE-Aging Inspection | 9/11/2012 | 9/11/2012 | 9/11/2012 | | DONE |
Bob Reichert
|
|
|
see doc expire
|
DOC - Permit Expired | 9/11/2012 | 9/11/2012 | 9/11/2012 | P | PASS |
Bob Reichert
|
|
|
new contractor did work, ok expire
|
ELE-Aging Inspection | 6/8/2012 | 6/8/2012 | 6/8/2012 | | DONE |
Bob Reichert
|
|
|
still waiting for call
|
ELE-Aging Inspection | 3/9/2012 | 3/9/2012 | 3/9/2012 | | DONE |
Bob Reichert
|
|
|
called, they will check and return call for status
|
Permanent Service | 6/6/2011 | 6/6/2011 | 6/6/2011 | P | FAIL |
Bob Reichert
|
|
|
Key to front door under a piece of Slate on the right hand side. reconnect inspection for idaho power - power off for a year. >> Inspection requested via web by Dave Koeppen called, apparently electrican has not been to job, told office would list violations on-line, BCC shall bring service up to code, shall provide grounding at incoming water pipe within 5' of entering structure,augment with 2 ground rods, provide abrasion protection for conductors entering enclosure, isolate neutral and ground at sub-panel,shall use 4 wires, shall provide range and dryer with 4-wire, and receptacles, shall provide correct panel schedule, water heater disconnect, fee due
|
Reinspection Fee (no hold) | 6/6/2011 | 6/6/2011 | 6/6/2011 | P | PASS |
Bob Reichert
|
|
|
Key to front door under a piece of Slate on the right hand side. reconnect inspection for idaho power - power off for a year. >> Inspection requested via web by Dave Koeppen see fail inspection
|
Application received | | | 6/6/2011 | | DONE |
|
|
|
This permit was created on the web by Dave Koeppen
|