Final | 8/10/2011 | 8/10/2011 | 8/10/2011 | P | PASS |
Bob Reichert
|
|
|
arthur Phone #: ###-#### moved in, couldn't check all receptacles, told owner to change a/c breaker, ok to final
|
Electrical Rough-In | 6/23/2011 | 6/24/2011 | 6/24/2011 | A | PASS |
Bob Reichert
|
|
|
arther please call 30 min before going out Phone #: ###-#### corrections made, ri ok
|
(F) Reprint permit | | | 6/15/2011 | | DONE |
Barbara Stitt
|
|
|
|
Electrical Rough-In | 6/13/2011 | 6/14/2011 | 6/14/2011 | P | FAIL |
Bob Reichert
|
|
|
Call 30min prior----Arthur Phone #: ###-#### met owner, left correction notice- BCC shall change room count to 5, all make-up shall be done, NEC 352.30 shall strap pvc within 3' of panel,110.26(F) there shall be no foreign piping in dedicated panel space, 334.23 shall protect wiring within 6' of attic access, 210.52 shall provide receptacles per code section, 300.4(A) edge of bored holes shall be within 1 1/4" of edge of framing member, 300.15 covers shall be accessible
|
Application received | | | 6/6/2011 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/6/2011 | | DONE |
|
|
|
|