Final | 7/8/2011 | 7/8/2011 | 7/8/2011 | A | PASS |
Daryl DeGrange
|
|
|
>> Inspection requested via web by Steve Craig final ok
|
Electrical Rough-In | 7/8/2011 | 7/8/2011 | 7/8/2011 | A | PASS |
Daryl DeGrange
|
|
|
Ceiling inspection >> Inspection requested via web by Steve Craig rough-in ok cover ceiling grid
|
Final | 7/6/2011 | 7/7/2011 | 7/7/2011 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Steve Craig No grid inspection has beed done. MC support wires shall be connected top and bottom. NEC 210.9 (B) (5) where receptacles are installed within(6ft.) of the outside edgeof the sink require GFCI protection
|
Electrical Rough-In | 6/9/2011 | 6/9/2011 | 6/9/2011 | P | PASS |
Daryl DeGrange
|
|
|
Steve Phone #: ###-#### rough-in ok corrections done
|
Electrical Rough-In | 6/8/2011 | 6/9/2011 | 6/9/2011 | A | FAIL |
Bob Reichert
|
|
|
Call Steve at ###-#### prior to inspection Phone #: ###-#### >> Inspection requested via web by Steve Craig called. left correction notice, NEC330.17 shall protect mc cable per 300.4(A)&(D), 330.30B shall strap mc within 12" of box, 348.30 A,B shall strap and support flex metal conduit, 358.26 there shall not be more than 360 degree bend in emt, BCC shall not support mc in valley of studs
|
Application received | | | 6/8/2011 | | DONE |
|
|
|
This permit was created on the web by Steve Craig
|