ELE-Aging Inspection | 6/12/2012 | 6/12/2012 | 6/12/2012 | | DONE |
Jack Frank
|
|
|
|
Final | 6/12/2012 | 6/12/2012 | 6/12/2012 | A | PASS |
Jack Frank
|
|
|
ther will be a new permit for remodel on existing house
|
ELE-Aging Inspection | 3/13/2012 | 3/13/2012 | 3/14/2012 | | CANC |
Jack Frank
|
|
|
|
Final | 8/17/2011 | 8/17/2011 | 8/17/2011 | A | PART |
Doug A Poedy
|
|
|
Want final on new addition only, thank you Phone #: ###-#### >> Inspection requested via web by Lloyd Looney. New addition ok.
|
Final | 8/16/2011 | 8/16/2011 | 8/16/2011 | P | NR |
Jack Frank
|
|
|
lloyd Phone #: ###-#### called left message
|
Permanent Service | 6/14/2011 | 6/14/2011 | 6/14/2011 | A | PASS |
Jack Frank
|
|
|
p/s u/g new ok
|
Rough-In Permanent Service | 6/13/2011 | 6/14/2011 | 6/14/2011 | A | PASS |
Jack Frank
|
|
|
Need to reinspect correction items & ufer grounding electrode Phone #: ###-#### >> Inspection requested via web by Lloyd Looney
|
Rough-In Permanent Service | 6/9/2011 | 6/10/2011 | 6/10/2011 | A | FAIL |
Bob Reichert
|
|
|
Asking for service & approval for cover for new addition. The existing home remodle will be on a seperate permit. Phone #: ###-#### >> Inspection requested via web by Lloyd Looney called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 250.52(A)(3) shall provide concrete encased electrode, 334.80 shall not run over 2 nm cables out of panel without derating
|
Application received | | | 6/9/2011 | | DONE |
|
|
|
This permit was created on the web by Lloyd Looney
|