Final | 8/5/2011 | 8/8/2011 | 8/8/2011 | A | PASS |
Daryl DeGrange
|
|
|
Key inside front w/p receptacle box for access Phone #: ###-#### >> Inspection requested via web by daniel bibikov final ok
|
Final | 8/5/2011 | 8/5/2011 | 8/5/2011 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 110.12 Mechanical execution of work Main bath two gang box, Several extra holes drilled in two locations for fishing additional nm cable into switch box do to incomplete circuitry. The outer NM cable sheath shall extend at least 1/4 inch inside device enclosure
|
Final | 8/4/2011 | 8/5/2011 | 8/5/2011 | A | FAIL |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov. NEC 210.8 Garage door opener must be on GFCI. NEC 110.3 South hallway switch not working.
|
Permanent Service | 8/1/2011 | 8/1/2011 | 8/1/2011 | P | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov. P/S Connect ok.
|
Rough-In Permanent Service | 6/23/2011 | 6/23/2011 | 6/23/2011 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov rough-in ok but no permanent service- overhead service mask needs to be at least 2 in IMC if going to be point of attachment.
|
Application received | | | 6/23/2011 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|