Final | 9/26/2011 | 9/26/2011 | 9/26/2011 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov final ok
|
Final | 9/25/2011 | 9/26/2011 | 9/26/2011 | A | FAIL |
Daryl DeGrange
|
|
|
Key code for acess 6445 enter Phone #: ###-#### >> Inspection requested via web by daniel bibikov NEC 210.8(A) (2) All 125 volt 15 and 20 ampere receptacles in an garage,shall be GFCI protected. Garage door opener Nec 406.8(B) (1) All 125 volt 15 and 20 amper outdoor receptacles shall be listed weather-resistance type. Rear patio receptacle. Missing wall plates
|
Electrical Rough-In | 8/4/2011 | 8/4/2011 | 8/4/2011 | P | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov. Ok to cover.
|
Permanent Service | 8/4/2011 | 8/4/2011 | 8/4/2011 | P | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov. P/S Connect ok.
|
Rough-In Permanent Service | 7/29/2011 | 7/29/2011 | 7/29/2011 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov NEC 300.4(A) Edge of bored holes and NM cable shall be 1 1/4 from edge of framing members NEC 334.30 Shall staple NM cable every 4 1/2 feet NEC 210.52 Any wall space of 2 ft. or more in width shall have an receptacle. Dinning room needs an box set for fixture
|
Application received | | | 7/29/2011 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|