Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberELE11-01963
StatusFinaled
Name ROBERT PETERSON
Site Address 2425 W BANNOCK ST
Project Name 
Customer Number 
ePlanReviewNo
Description
new service to garage
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/7/20119/8/20119/8/2011APASS
DetailsDaryl DeGrange
Robert Phone #: ###-#### final ok unattach garage
Final9/6/20119/7/20119/7/2011AFAIL
DetailsDaryl DeGrange
BOB-Please call at least 30 mins prior to inspection Phone #: ###-#### NEC 210.8(2) Garage shall have GFCI protection
Electrical Rough-In8/24/20118/25/20118/25/2011APASS
DetailsDaryl DeGrange
Robert Phone #: ###-#### rough-in ok cover
Electrical Rough-In8/24/20118/24/20118/24/2011PFAIL
DetailsDaryl DeGrange
Trench covered before inspection, contractor dug up two two locations. NEC 3004 NM cable shall be stapled within 12 inches of an receptacle or light box. NEC 334.4 (A) (B) Edge of bored holes and NM cable shall be 1 1/4 from edge of framimg member. NEC 334.25 Bending radius The radius of the curve of the inner edge of any bend during or after installation shall not be less than five times the diameter of the cable
Conference8/24/20118/24/20118/24/2011PDONE
DetailsDaryl DeGrange
Talked with general contractor-home owner not available-wiring allready installed before conference meeting. some electrical corrections needed before covering
Application received  8/24/2011  
Issue PAID IN FULL permit  8/24/2011 DONE