Final | 12/13/2011 | 12/13/2011 | 12/13/2011 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Rick Beckman corrections made, ok final
|
Final | 12/2/2011 | 12/2/2011 | 12/2/2011 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Rick Beckman called, left correction notice, NEC 344.30 shall securely support riser within 3' of panel, 250.94 shall provide intersystem bond bar, 210.52(A)(2) shall provide outlet in 2' wall space under bar type counter, 406.4 shall securely mount receptacles
|
Fees Due Hold | 10/13/2011 | | 10/24/2011 | | DONE |
Christina Prado
|
|
|
|
Rough-In Permanent Service | 9/1/2011 | 9/2/2011 | 9/2/2011 | A | PASS |
Bob Reichert
|
|
|
Jason will be the contact for today Phone #: ###-#### >> Inspection requested via web by Rick Beckman ri ok, p/s o/h n ok, 2 meters req'd
|
Application received | | | 9/1/2011 | | DONE |
|
|
|
This permit was created on the web by Rick Beckman
|