Final | 10/20/2011 | 10/20/2011 | 10/20/2011 | A | PASS |
Jack Frank
|
|
|
|
Permanent Service | 10/19/2011 | 10/20/2011 | 10/20/2011 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt needs to check range and dryer and install 4 wire pigtails and recepts
|
Permanent Service | 10/10/2011 | 10/10/2011 | 10/10/2011 | P | FAIL |
Bob Reichert
|
|
|
John, ###-#### called, NEC 310.15 shall provide correct wire size, 4/0 aluminum, 225.19 shall provide 8' clearance over roof, 250.32 shall provide 4 wire feeder and isolate neutral and ground in house panel
|
Issue permit | | | 10/10/2011 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/10/2011 | | DONE |
|
|
|
This permit was created on the web by John VanZandt
|