Final | 1/26/2012 | 1/26/2012 | 1/26/2012 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson corrections made, ok final
|
Final | 1/25/2012 | 1/26/2012 | 1/26/2012 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson called, corrections not made, fee due
|
Reinspection Fee (no hold) | 1/26/2012 | 1/26/2012 | 1/26/2012 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson corrections not made
|
Reinspection Fee (no hold) | 1/26/2012 | 1/26/2012 | 1/26/2012 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson corrections not made
|
Final | 1/25/2012 | 1/25/2012 | 1/25/2012 | P | FAIL |
Bob Reichert
|
|
|
theran Phone #: ###-#### call, left message, people moved in, did part of outlets only, shall install front receptacle, add outlet cover in garage, outlets in master bedroom shall work
|
Electrical Rough-In | 10/27/2011 | 10/27/2011 | 10/27/2011 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson corrections made, ri ok
|
Electrical Rough-In | 10/24/2011 | 10/24/2011 | 10/24/2011 | P | FAIL |
Bob Reichert
|
|
|
Key under mat at front door Phone #: ###-#### >> Inspection requested via web by Therrin Robertson called, left correction notice, NEC 250.86 shall ground metal box,use ground screw, 314.23(B) shall not screw metal box to stud with screw inside box, shall rigidly mount box, 300.4 edge of nm cable shall be 1 1/4" from edge of framing member, 334.30 shall staple nm cable within 12" of panel, 300.15 shall provide boxes for termination of nm cale, 210.52(E) shall install receptacle at front of dwelling, 210.52 shall provide outlet such that no point is over 6' from outlet along floor line
|
Rough-In Permanent Service | 10/14/2011 | 10/14/2011 | 10/14/2011 | P | CANC |
Bob Reichert
|
|
|
Service change --Rough in Phone #: ###-#### >> Inspection requested via web by Therrin Robertson see p/s only
|
Permanent Service | 10/14/2011 | 10/14/2011 | 10/14/2011 | P | PASS |
Bob Reichert
|
|
|
p/s u/g rec ok
|
Issue PAID IN FULL permit | | | 10/14/2011 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/14/2011 | | DONE |
|
|
|
This permit was created on the web by Therrin Robertson
|