Final | 11/10/2011 | 11/10/2011 | 11/10/2011 | P | PASS |
Bob Reichert
|
|
|
re inspection for heat pump wiring, any questions call Clint @###-#### >> Inspection requested via web by Andy Rose corrections made, ok final
|
Final | 10/28/2011 | 10/31/2011 | 10/31/2011 | A | FAIL |
Daryl DeGrange
|
|
|
wired new heat pump, any questions call Clint @ ###-####. Please call Copper @ ###-#### to set time to meet to be let in to house. Phone #: ###-#### >> Inspection requested via web by Andy Rose Outdoor unit requires service outlet. NEC 400.8 (2) Uses not permitted SO cord not permitted to run through walls.
|
Issue PAID IN FULL permit | | | 10/27/2011 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/27/2011 | | DONE |
|
|
|
This permit was created on the web by Andy Rose
|