Final | 6/22/2012 | 6/22/2012 | 6/22/2012 | P | PASS |
Bob Reichert
|
|
|
Please call prior for access -- Don Phone #: ###-#### ok final
|
Final | 4/3/2012 | 4/4/2012 | 4/4/2012 | A | FAIL |
Bob Reichert
|
|
|
don please call for access Phone #: ###-#### met owner, shall provide tamper proof receptacles, tighten loose receptacle, id breakers, outdoor receptacle shall be weather resistant
|
Electrical Rough-In | 12/14/2011 | 12/14/2011 | 12/14/2011 | P | PASS |
Bob Reichert
|
|
|
corrections made, ri ok
|
Electrical Rough-In | 12/12/2011 | 12/13/2011 | 12/13/2011 | A | NR |
Bob Reichert
|
|
|
don Phone #: ###-#### met owner, reviewed correction notice, will fix and recall
|
Electrical Rough-In | 12/12/2011 | 12/12/2011 | 12/12/2011 | P | FAIL |
Bob Reichert
|
|
|
Please call 20min prior for access---Don Phone #: ###-#### corrections not made
|
Electrical Rough-In | 12/8/2011 | 12/9/2011 | 12/9/2011 | P | FAIL |
Bob Reichert
|
|
|
don please call before going out- Phone #: ###-#### called, left correction notice, NEC 300.14 shall provide 6" free conductor at box, 250.86 shall provide ground screw in metal boxes, 300.4(A)(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 314.16 shall not exceed box fill, 334.30 shall staple nm within 12" of box or314.17(C) shall staple nm within 8" if more than 1 nm enters box, BCC all make-up shall be done
|
Conference | 11/14/2011 | 11/14/2011 | 11/14/2011 | P | DONE |
Bob Reichert
|
|
|
Please call 20min prior for access---Don Phone #: ###-#### talked about room addition wiring, when to call for ri, owner only doing wiring
|
Application received | | | 11/10/2011 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 11/10/2011 | | DONE |
Barbara Stitt
|
|
|
|