DOC - Permit Expired | 2/29/2012 | 2/29/2012 | 2/29/2012 | P | PASS |
Daryl DeGrange
|
|
|
?s call 415 Electrical contractor done with job at rough-in stage, other electrical contractor taking over job to completion permit final ok
|
Permanent Service | 12/14/2011 | 12/14/2011 | 12/14/2011 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey p/s u/g rec ok meter pac
|
Permanent Service | 12/13/2011 | 12/13/2011 | 12/13/2011 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey NEC Table 250.66 Water pipe bond shall be 2/0 cu. or 4/0 alu
|
Electrical Rough-In | 12/7/2011 | 12/7/2011 | 12/7/2011 | P | PASS |
Daryl DeGrange
|
|
|
If there is a way to give me 60 min notice before you arrive that would be great. Phone #: ###-#### >> Inspection requested via web by Neal Rumsey rough-in ok cover all 6 units
|
Electrical Rough-In | 11/30/2011 | 11/30/2011 | 11/30/2011 | P | NR |
Daryl DeGrange
|
|
|
jeff Phone #: ###-#### General contractor requested to cancel rough-in inspection do to not being ready.
|
Electrical Rough-In | 11/29/2011 | 11/29/2011 | 11/29/2011 | P | FAIL |
Daryl DeGrange
|
|
|
Jeff Phone #: ###-#### NEC 300.4(A) Shall not staple NM cable within 1 1/4 of the edge of framing members. NEC 334.30 Shall staple NM cable within 12 inches of box
|
Electrical Rough-In | 11/18/2011 | 11/18/2011 | 11/18/2011 | P | FAIL |
Daryl DeGrange
|
|
|
Jeff Phone #: ###-#### In need of restapling romex for 1 1/4 ,nailplates, checking receptacle spacing
|
Issue PAID IN FULL permit | | | 11/14/2011 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/14/2011 | | DONE |
|
|
|
This permit was created on the web by Neal Rumsey
|
Reinspection Fee (no hold) | 11/29/2011 | 11/29/2011 | | P | |
Daryl DeGrange
|
|
|
|