First Notice | 12/2/2011 | 12/2/2011 | 3/15/2012 | | DONE |
Doug A Poedy
|
|
|
|
Final | 12/2/2011 | 12/2/2011 | 12/2/2011 | P | PASS |
Doug A Poedy
|
|
|
|
Final | 12/2/2011 | 12/2/2011 | 12/2/2011 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by Cyndi Dale called violations not corrected shall not use ceiling support wires to secure high and low voltage cables, also shall not use fixtures support wires to secure cables, and still need to remove all abandoned cables
|
Reinspection Fee (no hold) | 12/2/2011 | 12/2/2011 | 12/2/2011 | P | PASS |
Jack Frank
|
|
|
fee due violations not corrected
|
Final | 12/1/2011 | 12/2/2011 | 12/2/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Cyndi Dale called, initialled correction notice for parts corrected, shall leave ceiling tiles out for inspection
|
Final | 11/30/2011 | 12/1/2011 | 12/1/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Cyndi Dale called, left correction notice, BCC shall provide approved set of plans, and occupancy card, NEC 406.5,404.9 shall install switch and receptacle covers, 300.11 no wiring shall be supported by ceiling grid or tiles, 725.25 shall remove abandoned low voltage wiring
|
Electrical Rough-In | 11/16/2011 | 11/17/2011 | 11/17/2011 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by Cyndi Dale walls both spaces 100&101
|
Issue PAID IN FULL permit | | | 11/16/2011 | | DONE |
Barbara Stitt
|
|
|
|
Owner Supplied Equipment | | | 11/14/2011 | | |
|
|
|
|
Application received | | | 11/14/2011 | | DONE |
|
|
|
This permit was created on the web by Cyndi Dale
|