Final | 1/23/2012 | 1/23/2012 | 1/23/2012 | P | PASS |
Bob Reichert
|
|
|
Garage Entrance Code 1968E Phone #: ###-#### >> Inspection requested via web by Alan Lusk corrections made, ok final
|
Final | 1/23/2012 | 1/23/2012 | 1/23/2012 | P | PASS |
Bob Reichert
|
|
|
Garage Entrance Code 1968E Phone #: ###-#### >> Inspection requested via web by Alan Lusk corrections made, ok final
|
Final | 1/20/2012 | 1/23/2012 | 1/23/2012 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk called, shall strap risers, tighten receptacle mbr, add closet fixture east side
|
Rough-In Permanent Service | 11/23/2011 | 11/23/2011 | 11/23/2011 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 11/21/2011 | 11/23/2011 | 11/23/2011 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk called, left correction notice, NEC 210.52(A)(2) shall install receptacles in wall space such that no point is over 6' from outlet, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member or add steel plates, BCC shall provide boxes for nm cable, shall provide approved set of plans
|
Issue PAID IN FULL permit | | | 11/15/2011 | | DONE |
|
|
|
|
Application received | | | 11/14/2011 | | DONE |
|
|
|
This permit was created on the web by Alan Lusk
|