Final | 7/8/2013 | 7/8/2013 | 7/8/2013 | P | PASS |
Daryl DeGrange
|
|
|
Tom Phone #: ###-#### bonding of metal fencing to pool and hot tub equipment complete, final ok
|
Final | 7/2/2013 | 7/3/2013 | 7/3/2013 | A | FAIL |
Daryl DeGrange
|
|
|
tom Phone #: ###-#### NEC 680.62(B)(4) Bonding of metal structures within 5 ft. of pool and motorized tub (Fencing)
|
Electrical Rough-In | 5/28/2013 | 5/29/2013 | 5/29/2013 | A | PASS |
Rock A. Hudson
|
|
|
Potting inspection for two pool lights. Go through gate and watch for small dogs. Thank You Phone #: ###-#### >> Inspection requested via web by Eric Brown Rough in ok cover
|
ELE-Aging Inspection | 3/15/2013 | 3/15/2013 | 3/15/2013 | | DONE |
Rock A. Hudson
|
|
|
called contractor left message
|
ELE-Aging Inspection | 12/14/2012 | 12/14/2012 | 12/14/2012 | | DONE |
Rock A. Hudson
|
|
|
Still under construction
|
Electrical Rough-In | 8/27/2012 | 8/28/2012 | 8/28/2012 | A | PASS |
Daryl DeGrange
|
|
|
TOM Phone #: ###-#### rough-in ok cover pool bonding
|
Electrical Rough-In | 8/23/2012 | 8/24/2012 | 8/24/2012 | A | CANC |
Daryl DeGrange
|
|
|
tom Phone #: ###-#### requested by contractor
|
Electrical Rough-In | 8/23/2012 | 8/23/2012 | 8/23/2012 | P | FAIL |
Doug A Poedy
|
|
|
Bond inspection-Tom Phone #: ###-####. Light bond not done.
|
Electrical Rough-In | 8/16/2012 | 8/16/2012 | 8/16/2012 | P | PASS |
Daryl DeGrange
|
|
|
Tom-On the pool Phone #: ###-#### rough-in ok cover after pool control conduit reinstalled to NEC 352.24 & 352.26
|
Electrical Rough-In | 2/2/2012 | 2/2/2012 | 2/2/2012 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by mike brown rough-in ok cover remodel
|
Electrical Rough-In | 12/1/2011 | 12/1/2011 | 12/1/2011 | P | PASS |
Daryl DeGrange
|
|
|
Tom (trench inspection) Phone #: ###-#### rough-in ok cover trench (pool equipment)
|
Issue PAID IN FULL permit | | | 11/30/2011 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/30/2011 | | DONE |
|
|
|
This permit was created on the web by mike brown
|