First Notice | 12/21/2011 | 12/21/2011 | 12/29/2011 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Dan Mitchell
|
Final | 12/21/2011 | 12/21/2011 | 12/21/2011 | P | PASS |
Bob Reichert
|
|
|
Corrections made & ready for re-inspection. That riser was installed by others, but I strapped it. Thanks, Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell corrections made, ok final
|
Final | 12/16/2011 | 12/21/2011 | 12/21/2011 | A | FAIL |
Bob Reichert
|
|
|
Key is above door or exterior light, please replace it when done. Thanks, Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell called, shall strap riser, shall provide gfci that functions
|
Rough-In Permanent Service | 12/7/2011 | 12/8/2011 | 12/8/2011 | A | PASS |
Bob Reichert
|
|
|
Correction made to flex run. UL stickers are on top of the VFD''S. Thanks, Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell corrections made, ri ok, p/s u/g n ok
|
Rough-In Permanent Service | 12/7/2011 | 12/7/2011 | 12/7/2011 | P | FAIL |
Bob Reichert
|
|
|
Key is above the door frame, please lock when done and replace the key to above the doorway. Please notify Idaho Power when you are finished so they will energize this service. I will request a Final after we test run everything. Thank you, Dan. Phone #: ###-#### >> Inspection requested via web by Dan Mitchell called, told to find listings for equipment, conduit has too many bends, did not see make-up for boxes
|
Issue PAID IN FULL permit | | | 12/7/2011 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/7/2011 | | DONE |
|
|
|
This permit was created on the web by Dan Mitchell
|