Permit NumberELE11-02819
StatusFinaled
Name BROTHERS ELECTRIC
Site Address 1918 W RIDENBAUGH ST
Project Name 
Customer Number340 2173
ePlanReviewNo
Description
Electrical Permit - New
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/15/20123/15/20123/15/2012PPASS
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by TRAVIS WARFIELD final ok
Final3/12/20123/14/20123/14/2012PFAIL
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by TRAVIS WARFIELD NEC 410.16 Does not meet minmun clearance distance 12in for surface-mounted incandescent. Basement bedroom closet luminaire
Permanent Service12/23/201112/23/201112/23/2011APASS
DetailsDaryl DeGrange
p/s o/h rec ok
Electrical Rough-In12/22/201112/23/201112/23/2011APASS
DetailsDaryl DeGrange
all so need the service inspected Phone #: ###-#### >> Inspection requested via web by TRAVIS WARFIELD rough-in ok cover
Electrical Rough-In12/21/201112/22/201112/22/2011AFAIL
DetailsDaryl DeGrange
Phone #: ###-#### >> Inspection requested via web by TRAVIS WARFIELD NEC 300.4(A) Edge of bored holes and NM cable shall be at least 1 1/4 from edge of framing member. NEC 334.30 Shall staple NM cable within 12 inches of box NEC 210.52 (2) small appliance branch circuit shall have no other outlets
Issue PAID IN FULL permit  12/14/2011 DONE
Payment received via Govolutions
Application received  12/14/2011 DONE
This permit was created on the web by TRAVIS WARFIELD