Final | 9/25/2012 | 9/28/2012 | 9/28/2012 | P | PASS |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by Matthew White
|
Final | 8/28/2012 | 8/29/2012 | 8/29/2012 | A | FAIL |
Doug A Poedy
|
|
|
Phone #: ###-#### >> Inspection requested via web by Matthew White. NEC 352.30 A Need to strap both conduits. Earth is not considered first support. Ground can settle and pull pipe and connector apart.
|
Permanent Service | 1/12/2012 | 1/12/2012 | 1/12/2012 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### >> Inspection requested via web by Matthew White p/s u/g new ok
|
Issue PAID IN FULL permit | | | 1/10/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/10/2012 | | DONE |
|
|
|
This permit was created on the web by Matthew White
|
First Notice | 9/28/2012 | 9/28/2012 | | | |
Doug A Poedy
|
|
|
|